EcoStruxure Transformer Expert with H2Sense Integrated Sensor is only available in Australia as beta release.
The key features of the H2 Integrated Sensor are listed below:
- Integrated H2 sensor
- State-of-the-art PD analysis hardware design
- Increased PD sensitivity
- High volume data collection and edge processing
- Acoustic sensors capable of structural analysis
- Real Time Spectrum Analysis
Planning Guide
Please follow the standard EcoStruxure Transformer Sensor Planning Guide with exception of below mentioned steps.
Step 4.2 Probe Diameter
Ensure the valve will accommodate the 18mm diameter of the sensor probe.
Step 6 Determine the the Length
The H2 Integrated Sensor is only available in 340 mm length. Depending on the valve length at the installation point, additional spacers may be require to reduce the effective length of the probe.
An oil sample valve may be required if the installation of the sensor removes access to the sample point. This will alter the effective probe length. See Installation: Oil Sample Valve.
Effective Length with Oil Sample Valve = 220 mm