EcoStruxure Transformer Expert with H2Sense Integrated Sensor is only available in Australia as beta release.
The key features that makes the sensor distinct from standard sensor are mentioned below:
- Integrated H2 sensor
- State of the art PD analysis hardware design
- Increased PD sensitivity
- High volume data collection and edge processing
- Acoustic sensors capable of structural analysis
- Real Time Spectrum Analysis
Planning Guide:
Please follow the standard EcoStruxure Transformer Sensor Planning Guide with exception of below mentioned points.
Step 4.2 Probe Diameter
Ensure the valve will accommodate the 18mm diameter of the sensor probe.
Step 6 Determine the The Length
The sensor is only available in 340mm length. Depending on the valve length additional spacers may be require to reduce the effective length of the probe.
An oil sample valve may be required if the installation of the sensor removes access to the sample point. This will alter the probe length. See Installation: Oil Sample Valve.
Effective Length with Oil Sample Valve = 220mm